NC Machinery Logo

336 Excavator

  • Specs Summary
  • Minimum Rating
    ( )
  • Maximum Rating
    ( )
  • Emissions/Fuel Strategy
    ( )
  • Voltage
    ( )

C32 (50 Hz) with Upgradeable Packaging

The C32 with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.
  • Minimum Rating ( )
  • Maximum Rating ( )
  • Emissions/Fuel Strategy ( )
  • Voltage ( )
  • Frequency ( )
  • Speed ( )
  • Duty Cycle ( )
  • Engine Model ( )
  • Bore 5.71 in (145 mm)
  • Stroke 6.38 in (162 mm)
  • Displacement 1958.9 in³ (32.1 l)
  • Compression Ratio ( )
  • Aspiration ( )
  • Fuel System ( )
  • Governor Type ( )
  • Length - Maximum 179.2 in (4551 mm)
  • Width - Maximum 87.8 in (2231 mm)
  • Height - Maximum 85.6 in (2175 mm)
  • Length - Minimum 165.3 in (4198 mm)
  • Width - Minimum 66.3 in (1684 mm)
  • Height - Minimum 85.1 in (2162 mm)
  • Dry Weight - Genset (minimum) 14680 lb (6859 kg)
  • Dry Weight - Genset (maximum) 17855 lb (8099 kg)

Standard Equipment

Air Inlet System

  • Single element canister type with service indicator

Control Panel

  • EMCP 4.2
  • Warning Shutdowns
  • Digital Indicators
  • Control Features
  • Communications
  • Programmable Protective Relaying Functions

Cooling System

  • Radiator fan and fan drive
  • Low coolant level sensor
  • ATAAC
  • Coolant drain line with valve
  • Fan and belt guards
  • Caterpillar Extended Life Coolant

Exhaust System

  • Exhaust manifold - Dry
  • 203 mm (8 in) ID round flanged outlet

Fuel System

  • Fuel priming pump
  • Primary fuel filter with water separator
  • Fuel cooler
  • Secondary fuel filters

General

  • RH Service
  • Caterpillar Yellow with high gloss black rails & radiator
  • Flywheel and flywheel housing-SAE
  • SAE Standard Rotation

Generators and Attachments

  • Reactive droop
  • Winding temperature detectors
  • Class H temperature rise at 40C ambient
  • Busbar connections, top center mounted, top cable entry
  • Permanent magnet
  • NEMA Class H insulation
  • Salient pole
  • IEC standard hole pattern
  • 6 Lead
  • Integrated voltage regulator (IVR)
  • 3 Phase brushless
  • Internal excitation

Governing System

  • ADEM(tm) A4

Lube System

  • Gear type lube oil pump
  • Integral lube oil cooler
  • Lubricating oil
  • Oil filter, filler and dipstick
  • Oil drain lines and valve
  • Fumes disposal

Mounting System

  • Rails - engine/generator/radiator mounting
  • Rubber anti-vibration mounts

Power Termination

  • Busbar

Starting / Charging System

  • 45 amp charging alternator
  • Battery, rack and cables
  • 24-volt electric starting motor
  • Battery disconnect switch

Optional Equipment

Control System

  • Expansion I/O module
  • EMCP 4.3, EMCP 4.4
  • Remote annunciator module
  • Remote monitoring software
  • Local annunciator module
  • Remote annunciator module
  • EMCP (4.2) (4.3) (4.4)
  • Local annunciator module

Engine Options

  • Radiator duct flange
  • Exhaust guards / shields
  • Heavy duty electric starting motors
  • Dual element air cleaners
  • Heavy duty air cleaners
  • Muffler (industrial grade)

Engine System

  • Heavy duty electric starting motors
  • Battery charger (10 amps)
  • Spring type anti-vibration mounts (95% efficient)
  • Heavy duty batteries
  • Heavy duty air cleaners
  • Dual element air cleaners
  • Exhaust guards / shields
  • Muffler (industrial grade)
  • Radiator duct flange
  • Jacket water heater
  • Rubber anti-vibration mounts (90% efficient)

Extended Service Contract

  • 2 Year Extended Service Contract (ESC)
  • 3 Year Extended Service Contract (ESC)
  • 5 Year Extended Service Contract (ESC)

Generators

  • Anti-condensation heaters
  • Winding: [ ] Random [ ] Random with coastal insulation [ ] Form
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
  • Generator stator and bearing temperature monitoring & protection
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Winding: [ ] Random [ ] Random with coastal insulation [ ] Form
  • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C

Power Termination

  • Circuit breaker, IEC listed (fully rated)
  • Bus bars
  • Circuit breaker, 100% Rated, UL Listed (fully rated)